⚡ Find the Best Battery, Solar Kit, E-Bike or Generator  ·  Capacity, output and cost per watt-hour, side by side

HomeCalculators › Solar Panel Angle Calculator

Solar Panel Angle Calculator

Enter your latitude and get the tilt that collects the most energy over a full year, plus the two seasonal settings worth knowing.

Your latitude sets the tilt. Pick a season to bias it.

Northern or southern — enter it as a positive number.
33.5degrees from horizontal

Year-round tilt ≈ (Latitude × 0.76) + 3.1°. Seasonal = Latitude ± 15°.

A solar panel angle calculator turns latitude into the tilt a fixed array should sit at, measured up from level ground. The answer runs a little shallower than your latitude: 25.9° at 30° north, 33.5° at 40°, 41.1° at 50°. Seasonal settings sit 15° either side.

How the solar panel angle calculator works

Two terms, and only one is something you look up.

  • Tilt is the angle between the panel face and level ground: flat on a roof is 0°, propped against a wall is 90°. Every figure here is measured that way.
  • Latitude is how far you are north or south of the equator, and it is the only input needed: it sets how high the sun climbs at midday. Enter it as a positive number in either hemisphere; a southern array takes the same tilt, pointed at true north.

The year-round answer lands shallower than latitude, and that is deliberate. Summer days are long and winter days short, so most of the year’s usable light arrives while the sun is high, and a flatter panel sees more of the open sky on an overcast day. The seasonal settings are blunter: 15° either side approximates the sun’s 23.4° swing between the solstices.

The mistake almost everyone makes: measuring from the wrong reference. Tilt is measured up from horizontal, never across from vertical. Set a panel 30° off a wall and you have built a 60° tilt: a midwinter setting for northern Canada, not a year-round one for Texas. Lay a phone inclinometer flat on the panel face.

Tilt angle by latitude

Degrees up from horizontal, facing true south (true north below the equator). The seasonal columns are 15° either side of latitude, floored at flat.

LatitudeFixed, year roundSummer settingWinter setting
10°10.7°25°
15°14.5°30°
20°18.3°35°
25°22.1°10°40°
30°25.9°15°45°
35°29.7°20°50°
40°33.5°25°55°
45°37.3°30°60°
50°41.1°35°65°
55°44.9°40°70°
60°48.7°45°75°
65°52.5°50°80°

The highlighted row is 40°, close enough to Denver and Philadelphia to be a US default. Round your latitude to the nearest whole degree: half a degree moves the answer under four tenths, which no bracket resolves.

Do not actually mount at 0°. The summer column bottoms out flat in the tropics because that is what the arithmetic says, but a flat panel holds water and dust, and soiling costs more than a perfect angle gains. Keep at least 10° on anything permanent.

Why tilt matters for portable power and solar

The wattage printed on a panel is measured with light arriving square on the face. Tilt decides how close you get in your own yard, and it is the one variable that costs nothing to change.

It matters most when the array is the bottleneck rather than the battery, which is normal with portable kit. A power station refills only as fast as the panels feed it, so a badly angled 400W array turns a one-day recharge into one that never catches up. Our solar sizing guide covers the panel side; the solar battery calculator covers storage.

Three installations sit well away from ideal:

  • RV and van roofs. Panels bolted flat sit at 0–5° and give up close to a tenth of the year’s output, far more in December when the sun barely clears the panel plane. A tilting bracket buys back more than a third panel would; see off-grid RV.
  • Balcony and railing arrays. A panel on railings is close to vertical, effectively a deep winter setting. Over a year that costs roughly a quarter to a third against optimal tilt, but it beats a shallow roof array in December, often the right trade for plug-in solar.
  • Folding suitcase panels. Most give two or three kickstand positions, not a continuous adjustment. Take the nearest table value, and when the choice is steeper or shallower, go steeper: steep panels stay cleaner and shed snow, which matters in the months a solar generator works hardest.

On the numbers. The tilt angles here are geometry and exact. The output percentages are modelled estimates, and your own site will vary.

Tilt angles for US cities

Latitudes are city centre. The winter column is where to move an adjustable array in November if outage season is the point.

CityLatitudeFixed, year roundWinter setting
Miami, FL25.8°22.7°40.8°
Houston, TX29.8°25.7°44.8°
Phoenix, AZ33.4°28.5°48.4°
Atlanta, GA33.7°28.7°48.7°
Los Angeles, CA34.1°29.0°49.1°
Denver, CO39.7°33.3°54.7°
New York, NY40.7°34.0°55.7°
Chicago, IL41.9°34.9°56.9°
Boston, MA42.4°35.3°57.4°
Minneapolis, MN45.0°37.3°60.0°
Seattle, WA47.6°39.3°62.6°
Anchorage, AK61.2°49.6°76.2°

Notice how little spread there is. Houston and Boston are 12° of latitude apart and their fixed tilts differ by under 10°. Anything between 25° and 35° sits within a couple of percent of optimal almost anywhere in the lower 48, which is why so many roof pitches are fine as built: a 5:12 pitch is 22.6°, a 6:12 is 26.6°.

Seasonal adjustment, and when it earns its keep

Moving an array twice a year, summer setting in spring and winter setting in autumn, is worth roughly 4% of annual output. Four changes adds a point or two; monthly is a rounding error.

In money the case collapses for a roof. On a 2kW array making around 2,800 kWh a year, 4% is about 112 kWh, or roughly $19 at 17 cents per kilowatt-hour, which justifies neither a ladder twice a year nor adjustable mounts. Three situations change that:

  • Ground mounts and portable panels. You are standing next to them anyway, so take the 4%.
  • Winter-critical systems. If the array exists to hold a battery up through storm season, annual total is the wrong thing to optimise. Set the winter angle and leave it there.
  • Snow country. A 60° panel sheds snow. A 20° panel collects it and produces nothing until somebody clears it, turning a modest tilt gain into a total loss for days.

Single-axis tracking gains more again, but it is a motorised structure, and on a backup system that is the wrong complexity. Buy another panel: a fixed second beats a tracked first on cost and reliability.

Direction and shade beat a few degrees of tilt

Tilt has a forgiving curve. Ten degrees off ideal costs one or two percent over a year, and twenty degrees four to six. That is why a table of round numbers is enough here.

Azimuth, the compass direction the panel faces, is less forgiving. You want true south, and being 90° out, facing due east or west, gives up close to 15–20% of annual output. True south is not magnetic south: a compass can read 15° or more off, in opposite directions on the two US coasts. Line up on a satellite map.

Shade beats both. A branch across one corner for two hours a day costs more than any plausible angle error, and on a series-wired string one shaded panel drags the rest down. If the only unshaded spot faces the wrong way, take it. The power station finder narrows the catalogue by solar input, and compare power stations sets the shortlist side by side.

Frequently asked questions

What angle should my solar panels be at?

For a fixed array, a little under three quarters of your latitude plus about three degrees, measured up from horizontal: 25.9° at 30°, 33.5° at 40°, 41.1° at 50°. Anything within 10° of that loses one or two percent a year, so an existing roof pitch is often fine.

Should the tilt angle just equal my latitude?

It is a fair approximation, but slightly steep. Tilt set equal to latitude gives up one to two percent against the flatter optimum, because long summer days put more of the year’s sunlight into the high-sun months. Start at latitude and shade down a few degrees.

What is the best solar panel angle for winter?

Latitude plus 15°: about 56° in New York, 55° in Denver, 63° in Seattle. The steeper angle points the panel at a low winter sun and sheds snow instead of collecting it. If the array is mainly for outage backup, leave it there.

Is it worth adjusting solar panels seasonally?

Only if the panels are easy to reach. Two adjustments a year gain roughly 4%, about 112 kWh on a 2kW array, or near $19 at typical US rates. Free money on a ground mount or a portable panel; not worth the ladder on a roof.

What angle should portable solar panels be at?

Use the kickstand preset nearest latitude minus 15° in summer and latitude plus 15° in winter. Most folding panels offer two or three positions, so exactness is not available. When the choice is steeper or shallower, pick steeper: steep panels stay cleaner and shed snow.

What angle should solar panels be on a flat roof?

Lower than the latitude answer, typically 10–20° on a ballasted frame. Steeper tilts catch wind, need more ballast, and force wider spacing so rows do not shade each other. Do not lay them truly flat though: dirt and standing water cost more than the tilt gains.

Next step. With the angle settled, the remaining questions are how much panel and how much battery. Our guide to choosing a size works both through from a daily energy figure.

Scroll to Top