VA to Watts Calculator
Volt-amps are what a UPS, a generator or an inverter is rated at; watts are what your equipment actually receives.
Apparent power to real power. The difference is the power factor.
Watts = VA × Power factor
To convert VA to watts, multiply the volt-amps by the power factor of the load. Many kVA-rated inverters and three-phase commercial generators are rated at a 0.8 power factor, so a 1,000VA unit delivers 800 real watts; consumer desktop UPS units are usually rated nearer 0.6–0.67, so a 1,000VA desktop UPS is typically 600–670W. Single-phase home generators are normally rated at 1.0, so their kVA and watt figures match, and a purely resistive load such as a heater also runs at 1.0: 1,000VA is a full 1,000W.
The formula, and what each term means
Three quantities are involved, and they are genuinely different things, not three names for one.
- Volt-amps (VA) are apparent power: circuit voltage multiplied by the current flowing through it. It is what the cable, the breaker and an inverter’s output stage must carry, whether or not that current achieves anything.
- Watts (W) are real power: the share that becomes heat, light or motion. It is what your meter bills you for and what drains a battery.
- Power factor (PF) is the ratio between them, a number between 0 and 1: watts divided by volt-amps, nothing more complicated. The Department of Energy’s power factor fact sheet defines it the same way and names inductive loads such as motors and transformers as the cause of a low one.
On alternating current, voltage and current do not always rise and fall together. An induction motor pulls current out of step with the voltage; a cheap switch-mode supply pulls it in distorted spikes. Either way some of the current does no work, and the power factor is the fraction that does. On DC there is no phase shift, so the power factor is 1 and the units are interchangeable.
The mistake almost everyone makes. Assuming any 1,500VA UPS will hold a 1,500W load. Most will not. Depending on the model it is rated between about 900W and 1,500W (CyberPower lists its PR1500LCD at 1,500VA/1,500W, while many desktop models are rated 900W–1,000W), and that watt figure is printed on the unit beside the VA figure. When a manufacturer gives you both numbers, use the printed watts. If a desktop UPS label gives only VA, assume 0.6, not 0.8.
VA to watts conversion table
Power factor is the only variable here, so the table gives four of them. Voltage does not appear at all: 120V, 230V and 240V produce identical answers. Use the 0.8 column for a kVA-rated inverter or a three-phase generator that prints no watt figure, because 0.8 is the convention behind many of their ratings. A single-phase home generator is normally rated at 1.0, so read it from the last column: its kVA figure is already its watts. Use 0.6 for a consumer desktop UPS whose label gives no watt figure (most are rated 0.6–0.67) or for a motor-heavy load, and 0.9 to 1.0 for modern electronics and anything purely resistive. Some online and pure-sine UPS units are rated at 0.9–1.0, but only the printed watt figure tells you which.
| Apparent power | PF 0.6 | PF 0.8 (inverter, three-phase genset) | PF 0.9 | PF 1.0 (single-phase generator) |
|---|---|---|---|---|
| 100VA | 60W | 80W | 90W | 100W |
| 350VA | 210W | 280W | 315W | 350W |
| 500VA | 300W | 400W | 450W | 500W |
| 650VA | 390W | 520W | 585W | 650W |
| 750VA | 450W | 600W | 675W | 750W |
| 1,000VA | 600W | 800W | 900W | 1,000W |
| 1,200VA | 720W | 960W | 1,080W | 1,200W |
| 1,500VA | 900W | 1,200W | 1,350W | 1,500W |
| 2,000VA | 1,200W | 1,600W | 1,800W | 2,000W |
| 2,200VA | 1,320W | 1,760W | 1,980W | 2,200W |
| 3,000VA | 1,800W | 2,400W | 2,700W | 3,000W |
| 5,000VA | 3,000W | 4,000W | 4,500W | 5,000W |
| 10,000VA | 6,000W | 8,000W | 9,000W | 10,000W |
Kilovolt-amps move the decimal and nothing else: a 5kVA three-phase generator is 5,000VA, or 4,000W at the standard 0.8, while a 5kVA single-phase generator rated at 1.0 is a 5,000W machine. If a nameplate quotes both figures, divide the watts by the volt-amps to recover the manufacturer’s own power factor and use that instead.
Real ratings from UPS, generator and inverter makers
The table above runs on conventions. These are the figures makers publish for their own products, taken from each maker’s spec page or sheet. Where a maker gives both numbers, the power factor is simply the watts divided by the volt-amps.
Five 1,500VA UPS units
| Model | VA rating | Watt rating | Power factor |
|---|---|---|---|
| APC Back-UPS Pro BR1500G | 1,500VA | 865W | 0.58 |
| APC Back-UPS Pro BR1500MS2 | 1,500VA | 900W | 0.60 |
| CyberPower CP1500AVRLCD3 | 1,500VA | 900W | 0.60 |
| CyberPower CP1500PFCLCD | 1,500VA | 1,000W | 0.67 |
| CyberPower PR1500LCD | 1,500VA | 1,500W | 1.0 |
Same VA rating, watts from 865W to 1,500W. The BR1500G sits just under the 0.6 rule of thumb, which is why a printed watt figure beats any assumption.
Generators and inverters
| Unit | Maker’s rating | Power factor | Real watts |
|---|---|---|---|
| Honda EU22i portable inverter generator | 1.8kVA rated, 2.2kVA max (Honda South Africa); 1,800W rated, 2,200W max (Honda UK) | 1.0 | 1,800W rated |
| Generac Guardian 22kW home standby, 240V single-phase | 22,000W on LP, 19,500W on natural gas; 91.7A at 240V on LP | 1.0 (printed) | 22,000W on LP |
| Generac SD050 industrial diesel | 50kW, 63kVA standby | 0.8 three-phase, 1.0 single-phase (printed) | 50,000W |
| Victron MultiPlus-II 12/3000/120-50 inverter/charger, 120V | 3,000VA continuous at 25°C (77°F) | 0.8 | 2,400W at 25°C, 2,200W at 40°C (104°F) |
The Honda shows what the 0.8 shortcut does to a single-phase generator: 1.8kVA × 0.8 is 1,440W, 20% under the 1,800W Honda prints for the same machine. The 0.8 convention belongs to three-phase commercial sets, where the SD050’s 63kVA headline is its 50kW divided by 0.8, and to inverters like the Victron, which also gives up output as it warms. One limit still applies to a generator rated at 1.0: current. Generac’s 91.7A at 240V is 22,000VA, so a motor load at a 0.8 power factor reaches that current at about 17,600W.
Why this conversion matters for portable power
Portable power stations are sold in watts and watt-hours. UPS units, many off-grid inverters and some generators are sold in VA or kVA. Anyone shopping for outage backup compares the two, which means doing this conversion whether they notice or not.
Replacing a UPS with a power station
A 1,500VA desk UPS sounds far larger than a 1,000W power station. It is usually smaller. At a 0.6 power factor that UPS is a 900W device holding a load for minutes; the power station is a 1,000W device holding it for hours. Compare watts with watts, never with VA. Browse power stations on continuous output, and for anything panel-level start with home battery backup instead.
Sizing against an inverter you already own
If the inverter in your RV, van or cabin is stamped in VA, convert before you add up appliance loads, because appliance labels are in watts. Mixing the two units is how people end up 20% over the limit and puzzled by a shutdown that looks unprovoked.
Solar, where the ratings run both ways
Grid-tie inverters and microinverters are held near unity power factor by connection rules, so their output rating in VA and in watts is usually the same number. Balcony systems are the trap: the hardware may be specified in VA while the export limit that applies to it is written in watts. Our introduction to plug-in solar covers the rest.
After that the rest is arithmetic: watts against the continuous output rating, watts multiplied by hours against the capacity in watt-hours. The power station finder filters on both at once, and the comparison tool puts candidates side by side.
A watt rating assumes a well-behaved load. An inverter is limited by current as well as by real power, so a low-power-factor load can trip a 1,000W unit while the wattmeter still reads under 1,000W. Read a continuous watt rating as the figure at or near unity power factor, and leave headroom for motors.
Power factor by device type
If you can measure the power factor, measure it: most plug-in energy monitors display it directly, and one reading beats any assumption here. Failing that, use these ranges. They are general engineering figures, not specifications for any particular product.
| Load | Typical power factor | Notes |
|---|---|---|
| Kettle, toaster, resistive heater | 1.0 | Pure resistance; VA and watts are identical |
| Incandescent bulb | 1.0 | Also pure resistance |
| Modern PC or server supply with active PFC | 0.95–0.99 | Correction is built in and works well |
| Older PC supply with no PFC | 0.6–0.7 | The origin of the 0.6 UPS convention |
| Laptop and phone chargers | 0.5–0.95 | Wide spread, small numbers either way |
| LED lighting | 0.5–0.9 | Cheap drivers sit at the bottom of the range |
| Refrigerator or freezer compressor | 0.6–0.8 | Worse at startup than when running |
| Air conditioner, pump, power tool | 0.7–0.9 | Induction motors; size for surge separately |
| Microwave oven | 0.6–0.9 | Depends heavily on the transformer design |
| Anything running on DC | 1.0 | No phase shift exists on DC |
The pattern without the table: heat is 1.0, motors around 0.8, cheap electronics unpredictable enough to be worth measuring.
Worked examples, and going the other way
A 1,500VA UPS. If the label also says 900W, the power factor is 0.6 and 900W is the answer. If it says 1,350W, the power factor is 0.9. If it says nothing, assume 0.6 and plan on 900W; 0.8 would overstate most desktop units.
A 3kVA off-grid inverter. 3,000VA at 0.8 is 2,400W of real power. Compare the appliance labels you intend to run with 2,400, not with 3,000.
Turning watts into runtime. VA contains no time, so it says nothing about how long anything lasts. Convert first, then divide capacity by draw. A 300W load on a 1,000Wh power station, allowing 15% for inverter losses, has about 850Wh to work with: 850Wh ÷ 300W ≈ 2 hours 50 minutes. The watts to kWh calculator handles the energy side.
Watts back to VA
Divide rather than multiply. This is the direction you need when appliance labels are in watts and the hardware is rated in VA.
| Real power | Apparent power at PF 0.8 | Apparent power at PF 0.9 |
|---|---|---|
| 300W | 375VA | 333VA |
| 500W | 625VA | 556VA |
| 800W | 1,000VA | 889VA |
| 1,000W | 1,250VA | 1,111VA |
| 1,200W | 1,500VA | 1,333VA |
| 1,500W | 1,875VA | 1,667VA |
| 2,000W | 2,500VA | 2,222VA |
| 3,000W | 3,750VA | 3,333VA |
Breakers, cables and the 80 percent rule
Wiring responds to current, which puts it on the VA side of this conversion rather than the watts side. A 120V, 15A circuit carries 1,800VA. For a continuous load, meaning anything drawing for three hours or more, US practice derates that by 80% to 1,440VA; a 20A circuit gives 2,400VA, or 1,920VA continuous.
Those ceilings are in volt-amps, which is the point. A 1,440VA load at a 0.7 power factor is barely 1,000W of useful output, and the breaker does not care that the rest achieved nothing. Working from a current reading instead, the amps to watts calculator covers that step.
Frequently asked questions
How do I convert VA to watts?
Multiply the volt-amps by the power factor of the load. With no better information use 0.8 for a kVA-rated inverter or a three-phase generator, so a 1,000VA rating becomes 800W; 0.6 for a consumer desktop UPS, so 1,000VA becomes 600W; and 1.0 for a single-phase home generator, whose kVA and watt ratings are the same number. If the device prints both a VA and a watt rating, use the printed watts: that figure is the manufacturer’s own rather than a rule of thumb.
Is 1000VA the same as 1000 watts?
Only for a purely resistive load such as a kettle or a heater, where the power factor is 1.0. For everything else the watts are lower, typically 600W to 900W depending on what is plugged in. On DC, volt-amps and watts genuinely are the same number.
How many watts is a 1500VA UPS?
Between about 900W and 1,500W depending on the model: 900W at a power factor of 0.6, 1,000W at 0.67, which is common on desktop units, and up to 1,500W on unity-rated models such as CyberPower’s PR1500LCD. The exact figure is printed beside the VA rating. Both limits apply at once, so the UPS stops at whichever it reaches first.
What power factor should I use if I do not know it?
For a kVA-rated inverter or a three-phase generator, use 0.8, the convention behind many of their nameplates. A single-phase home generator is normally rated at 1.0, so its kVA figure is already its watts. For a consumer desktop UPS, assume 0.6: most are rated 0.6–0.67, so 0.8 would overstate the watts available. Use 0.6 for a motor-heavy load too, and 0.95 or above for electronics with active power-factor correction. A watt rating printed on the label always beats any of these assumptions.
Why are UPS units and generators rated in VA instead of watts?
Because their real limit is current, not useful output. Transformers, wiring and switching devices heat up according to the current they carry, whether or not it does any work. Volt-amps describe that limit honestly; watts describe what the connected equipment receives.
Does the VA to watts conversion apply to batteries and solar panels?
No. Batteries, solar panels and DC circuits have no power factor, so volt-amps and watts are identical there. It matters only on the AC side: after the inverter in a power station, or at the output of a UPS, a generator or a grid-tie system.
Can I run a 1000W appliance on a 1500VA inverter?
Only if the inverter’s watt rating is 1,000W or more, which at 1,500VA means a power factor of 0.67 or better. Check the printed watt figure first, then the surge rating: a compressor drawing 1,000W while running can demand several times that at startup.
Next step. A watt figure on its own only sizes the inverter. To size the battery behind it, our power station sizing guide turns a list of loads into a capacity number.